Ace IndustrialHardware
Zimbabwe

Wire & Sheet Gauge Conversion Chart

SWG, AWG and sheet-metal gauges converted to millimetres, sheet weights, and metric cable sizes against AWG.
Workshop Reference Charts
acehardware.co.zw

Gauge conversion

Gauge to millimetres

GaugeSWG mmSWG inchAWG mmUS steel sheet mmGalvanised sheet mmSteel sheet kg/m²
08.230.3248.251---
17.620.37.348---
27.010.2766.544---
36.4010.2525.8276.073-47.7
45.8930.2325.1895.695-44.7
55.3850.2124.6215.314-41.7
64.8770.1924.1154.935-38.7
74.470.1763.6654.554-35.8
84.0640.163.2644.1764.2732.8
93.6580.1442.9063.7973.89129.8
103.2510.1282.5883.4163.5126.8
112.9460.1162.3053.0383.13223.8
122.6420.1042.0532.6572.75120.9
132.3370.0921.8282.2782.37217.9
142.0320.081.6281.8971.99114.9
151.8290.0721.451.7091.80313.4
161.6260.0641.2911.5191.61311.9
171.4220.0561.151.3671.4610.7
181.2190.0481.0241.2141.3089.5
191.0160.040.9121.0621.1568.3
200.9140.0360.8120.9121.0067.2
210.8130.0320.7230.8360.936.6
220.7110.0280.6440.7590.8536
230.610.0240.5730.6830.7775.4
240.5590.0220.5110.6070.7014.8
250.5080.020.4550.5310.6254.2
260.4570.0180.4050.4550.5493.6
270.4170.01640.3610.4170.5113.3
280.3760.01480.3210.3780.4723
290.3450.01360.2860.3430.4372.7
300.3150.01240.2550.3050.3992.4
310.2950.01160.227---
320.2740.01080.202---
330.2540.010.18---
340.2340.00920.16---
350.2130.00840.143---
360.1930.00760.127---

Notes and electrical wire

AWG copper wire

AWGDiameter mmArea mm²Copper Ω/km at 20 °C
08.25153.4750.322
26.54433.6310.513
45.18921.1510.815
64.11513.3021.296
83.2648.3662.061
102.5885.2613.277
122.0533.3095.211
141.6282.0818.285
161.2911.30913.174
181.0240.82320.948
200.8120.51833.308
220.6440.32652.962
240.5110.20584.213
260.4050.129133.904
280.3210.081212.916
300.2550.051338.55

Metric cable sizes and AWG

Metric cable mm²Solid dia. mmExact AWGNearest AWG
0.50.820.120
0.750.9818.418
11.1317.217
1.51.3815.415
2.51.7813.213
42.2611.211
62.769.49
103.577.27
164.515.25
255.643.33
356.681.82
507.980.30
Copper resistance is for solid conductors at 20 °C (resistivity 0.017241 Ω·mm²/m). For cable current ratings use the cable maker's tables or SANS / IEC 60364: rating depends on insulation, installation method and ambient temperature.